Electrical Panels

Incomer :
3 Phase 415 volts AC
630 Amps. MCCB
R, Y, B Indication lamps
Energy Meter
Enclosure :
M.S. CRCA 14/16 SWG
Powder-coated RAL 6035
Bus Bar Chamber
Electrolytic grade Al
Outgoing :
3 Phase 415 V 250 A MCCB
3 Phase 415 V 125 A MCCB
3 Phase 415 V 63 A MCCB
3 Phase 415 V 32 A MCCB
IP Rating :
IP 54 - Dust and Vermin Proof

Applications

Specifications

All the PCCs (power control centers) are made from MS CRCA sheets duly powder-coated, totally enclosed, rigid, floor mounted, cubical type suitable for operation on three phase phase, 415 volts, 50 Hz. The PCCs are designed to withstand the heaviest condition at site, with minimum expected ambient temperature of 45 degree Celsius, 80 percent humidity and dusty weather. Ingress Protection level varies from IP42 to IP55. Regular PCCs are assembled with switchgears selected in accordance with IS 13947 and IEC 60947 norms to cater to all industrial, commercial and infrastructural segment.